Skip links

GE ED0600NGD-5_6-HC12V132-S-50Hz-600V Natural Gas Generator Set 600KW

 

Generator Data Description
Fuel type
Natural gas
Equipment type
ED0600NG-5/6
Equipment configuration
Power supply+ Heat Dissipation System 
+ Control cabinet + Steel skid

base (ED0600NG-5/6)
Genset compliance with standard
ISO3046,ISO8528, GB2820, CE

Description

ED0600NGD-5/6 Natural gas generator sets 600KW 600V 50HZ

Model #: ED0600NG-5/6

(Engine Model :HC12V132N5)

Main configuration and features:

□  Highly efficient gas engine.

□ AC synchronous alternator.

□ Gas safety valve bank. Gas protection device against leakage is optional.

□ Cooling system suitable for ambient temperature up to 50℃.

□ Strict shop test for all gensets.

□ Industrial silencer with silencing ability of 12-20dB(A).

□ Advanced engine control system: ECI control system including: ignition system, speed control system, protection system, air/fuel ratio control system and cylinder temperature system.

□ With cooler and Temperature Control System to make sure the unit can work normally at 50℃ environment temperature.

□ Independent electrical control cabinet, remote control is available.

□ Multi-functional control system with simple operation.

□ Data communication interfaces integrated into control system.

□  Monitoring battery voltage and charging automatically.

 

Generator Data Description
Fuel type
Natural GAS
Equipment type
ED0600NG-5/6
Equipment configuration
Power supply+ Heat Dissipation System + Control cabinet + Steel skid

base (ED0600NG-5/6)
Genset compliance with standard
ISO3046,ISO8528, GB2820, CE

 

Continuous output
Load
50%
75%
100%
Power output            KW
300
450
600
Fuel consumption     KW
827
1219
1579
Efficiency in mains parallel mode
Continuous output
50%
75%
100%
Electrical efficiency      %
36.2
36.8
38.0
Current (A)/ 600V / F = 0.8
360
540
720

Special statement

This solution is only an example of a specific environment, and does not represent the final demand

technology, providing your specific needs and gas source data, we will tailor it for you.

Main Power Operating Data
Synchronous alternator
Delta, 3P4h
Frequency                                               Hz
50
Power factor
0.8
Rating (F) KVA prime power                   KVA
750
Generator voltage                                   V
600
Current                                                    A
720
Starter battery 24V, capacity required     Ah
200×2
Starter motor                                    kWel. / VDC
7.5 / 24

 

Genset performance data and manufacturing technology
Overload run-time at 1.1 times (hour)
1
Signal interference factor (TIF)
≤50
Voltage setting range
≥±5%
Signal harmonious factor (THF)
≤2%,as per BS4999
Steady-state voltage deviation
≤±2%
Manufacturing technology

● Special welded base frame, inner vibration isolators and design
 for whole lifting

● With high-class paint, endurable brightness as well resistance
 against abrasion and defacing

●  Installation manual, operation and maintenance manual wiring 
program




Standards and certificate

● ISO3046,ISO8528,GB2820

● GB2820BS5000PT99, AS1359

●  ISO9001:2016 Quality system certification

●  Alternator compliance withGB755, BS5000, VDE0530,

NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standard.
Transient-state voltage deviation
-10%~15%
Voltage recovery time (s)
≤2
Voltage unbalance
1%
Steady-state frequency regulation
±1.5%
Transient -state frequency regulation
-15%~10%
Frequency recovery time (s)
≤5
Steady-state frequency band
1.5%
Recovery time response (s)
0.5
Line Voltage Waveform Sine Distortion Ratio
≤ 5%

 

Emission data [1]
Exhaust flow rate (wet)
3024 kg/h
Exhaust flow rate (dry)
2380 Nm3/h
Exhaust temperature
500 ℃
Front side max. allowed exhaust back pressure
5kPa
Genset compliance with standard
ISO3046,ISO8528, GB2820,
Emission:
Standard
Option (as per requirement)
NOx, at 5% residual oxygen&100% load
< 2.187 g/kW.h
< 0.4 g/kW.h
CO, at 5% residual oxygen&100% load
< 2.843 g/kW.h
< 3.5 g/kW.h
NMHC, at 5% residual oxygen&100% load
< 0.546 g/kW.h
<0.285 g/kW.h

Environmental noise

Sound pressure level at a distance of up to 7 m (standard)90 dB (A) / No protective cover type
  • Based on dry exhaust value at the end of catalyst.
Fuel Data
Fuel
Natural gas [1]
Gas intake pressure
450kPa-700kPa
Methane volume content
≥ 90%
Low heat value (LHV)
Hu ≥ 31.4MJ/Nm3
Gas Consumption per hour at 50% load
83 m3
                                            at 75% load
122 m3
                                            at 100% load
158 m3
[1] After the Natural gas components need to be provided by users, the relevant data of the technical manual will be revised.

Gas hoses are ECER110 approved. Components in the gas train meet Directive 90/356/EWG.

 

Service
Oil level (ambient temperature is higher than minus
 5°C/ ambient temperature is lower than minus 5°C)[2]
API 15W-40 CF4 /API 10W-30 CF4
Lubricating oil capacity min./max.
N/A / 60L (Engine)
Equipment coolant usage volume min./max.
110L / 120 L
Coolant type
50% softened water and 50% anti-freezing solution
 (ethylene glycol, with the concentration of the anti-freezing solution 
between 40%-68% )
Maximum pressure loss in front of air cleaner
5  mbar
Combustion air temperature minimum /design
5 ℃ / 35℃
Installation room ventilation (inlet air volume flow )
>40000 m³/h

●The oil standard refers to factors such as local ambient temperature and air pressure.

 

AC Generator performance data
Gas engine data
Generator brand
Mecc
Engine brand
 DEUTZ
Motor type
ECO40 VL4C
Voltage(V)
600
Engine type
V12 cylinders, Exhaust turbocharger with water-cooled
 turbine housing
Rated (H) KW prime power
600
Bore x Stroke (mm)
132mm×145mm
Rated (H) KVA prime power
750
Displacement (L)
24
Alternator efficiency (%)
95.2
Compression ratio
12.0
Power factor
0.8
Rated output power
630kW/1500rpm
Wiring connection
3/4
Oil consumption max.
≤0.3 g/kW.hr
Rotor insulation class
H class
Min Intake flow (kg/h)
2880
Rated temperature-rise
F class
Ignition method
Electrically controlled single cylinder independent 
high-energy ignition Equivalent combustion, closed loop
Excitation method
Brush-less
Fuel control mode
Equivalent combustion, closed loop control
Rated speed(min-1)
1500
Speed regulation mode
Electrical regulate
Housing protection
IP23

Control system

The parallel control cabinet adopts ComAp InteliGen as the main control module. The function of this programmable control 
system includes engine protection and control, connection  between generator and generator or generator and grid, and
 communication, etc.

Main advantages
  • l Wide range of communication capabilities: connection via RS232,RS485,
  • CAN and on board USB; internet access using Ethernet,GPRS,3G or 4G;
  • support for Modbus (TCP/RTU) and SNMP(v1/ v2c-including traps); active SMS and emails in different languages.
  • l In-built PLC, complemented with a PLC monitoring tool in InteliConfig.11 inputs and 7 outputs on board.
  • l 2x 10 A binary output for cranking and fuel solenoid.
  • l Total remote monitoring. More I/Os available over plug-in or CAN modules (CM-BIO8-EFCP, Intli AN8, Inteli AINBTC,
    Inteli AIO9/1, Inteli lO8/8, IGS-PTM).
  • l Control the engine and AC alternator by one module and access to all measurement data in time-corresponding 
    manner.
  • 5 languages are optional. Up to 350 events can be recorded.

 

Control System
Brand
ComAp
Controller functions
One button for start and stop, Data display, Recording, Protection, Monitoring, etc.
Display functions
Speed, Oil pressure, Water temperature, Hours of operation, Current, Voltage, Frequency, Battery 
voltage, Active power, Reactive power, etc.
Protection functions
Automatic control and alarm functions: High water temperature, Low oil pressure, Over speed, Over
 current, AC/ DC voltage level, short circuit, etc.

 

Standard configuration
Engine Control:
Generator Control:
Other controls:
Lambda closed loop control

Ignition system

Electronic governor actuator

Start up control

Speed control

load control
Power control

RPM control(synchronous)

Load distribution (island mode)

Voltage control


Voltage tracking (synchronous)

Voltage control (island mode)

Reactive power distribution

(island mode)


Oil filling automatically

lntake valve control

Fan control
Early warning monitoring
Battery voltage

Generator data: U, l, Hz, kW, kVA, 
kVAr, PF, kWh, kVAh

Genset frequency
Engine Speed

Engine running time

Intake pressure temperature

Oil pressure
Coolant temperature

Measurement of oxygen 
content in exhaust gas

Ignition status inspection
Coolant temperature

Fuel gas inlet pressure
Protection functions
Engine protection
Alternator protection 
Busbar mains protection 
System protection
Low oil pressure

Speed protection

over speed/short speed

Starting failure

Speed signal lost


Reverse power

Overload

Overcurrent

Overvoltage

Under voltage

over/under frequency

Unbalanced current
Overvoltage

Under voltage

Over/under frequency

Phase sequence

ROCOF alarm


Alarm Protection Function

High coolant temperature

Charge fault

Emergency Stop

 

Scope of Supply
Engine
Generator
Canopy and base
Canopy and base
Gas engine

Ignition system

Lambda controller

Electronic governor

 actuator

Electrical start motor

Battery system
AC generator

H class insulation

AVR voltage regulator

PF control

PMG
Steel shell base frame Engine 
bracket Vibration isolators

Soundproof canopy (optional)

Dust filtration (optional)
Air circuit breaker Communication interfaces 
Electrical switch cabinet

Auto charging system
Exhaust system
Lubrication system
Standard voltage
Induction system
Exhaust silencer

Exhaust bellows
Oil filter

Sensor
600V
Air filter
Safety valve
Service and documents
Manual cut-off valve

450~700kPa pressure gauge

Gas filter

Safety Solenoid valve (anti-explosion type is optional)

Pressure regulator

Flame arrestor as (option) Natural gas leakage alarm
Tools package

Installation and operation manual

Maintenance manual

Software manual

Parts manual
Engine operation

Gas quality specification

Control system manual

After service guide

Standard package

 

Optional configuration
Engine
Generator
Lubrication system
Coarse air filter

Backfire safety control valve

Water heater
Generator Brand: Stamford, Leroy-Somer, MECC

Treatments against humidity and corrosion
Oil consumption measuring gauge

Fuel pump

Oil heater

Daily auxiliary oil tank
Electrical system
Gas supply system
Voltage
Remote monitoring Grid-connection

Remote control

Sensor
Gas flow gauge

Gas filtration

Pressure reducer

Gas pretreatment

Alarm system
415V

440V

460V
Service and documents
Exhaust system
Heat exchange system
Service tools

Maintenance and service parts
Three-way catalytic converter

Guard shield from touch

Residential silencer

Exhaust gas treatment
Emergency radiator

Electric heater

Heat recovery system

Thermal storage tank

Open frame weight dimensions:

Paints, Dimensions and Weights of the Genset—ED0600NG-5/6
Genset size (length * width * height), mm
3800×1870×2250
Genset dry weight (kg)
5500
Spraying Process
High quality powder coating (RAL 9016 & RAL 5017 & RAL 9017 )

Dimensions are for reference only.

Weight and dimensions of the container canopy structure:

Paints, Dimensions and Weights of the Genset—ED0600NGD 5/6
Genset size (length * width * height) mm
6098×2438×2591(3290 Installing the cooling system)
Genset dry weight(Silent Type) kg
8500
The cooling system weight(Silent Type) kg
Spraying Process
High quality powder coating

Data is subject to change without prior notice as new products are always developed. Please contact

local agent with any doubts or for more information.

Reviews

There are no reviews yet.

Be the first to review “GE ED0600NGD-5_6-HC12V132-S-50Hz-600V Natural Gas Generator Set 600KW”

Your email address will not be published. Required fields are marked *

Name *

Review *